Baur Shirla Cable Sheath Testing and Fault Locator
Mobile cable sheath testing and fault location and Fault pre-location and pin-pointing in a single device
- Data export via USB interface
- Mains and battery operated
- Simple operation and intuitive user interface
The Baur shirla sheath test and fault location device is used for cable and cable sheath testing, and for the pre-location and pin-pointing of cable sheath faults and cable faults due to earth contact.
The fault pre-location is based on the measuring bridge principle according to Murray and Glaser. The measuring bridge is dimensioned specially for power cables, but also enables pre-location for control and lighting cables. Zero balance and evaluation take place automatically. The fault distance is shown in meters. Various cable sections can be entered, thus increasing the accuracy of the measurement.
For fault pin-pointing, the Baur shirla generates a pulsed voltage, thereby permitting the use of the step voltage method. Using the "Step voltage" set of the protrac® pin-pointing system, cable sheath faults and other faults due to earth contact can be located quickly and accurately
Functions
- Cable and cable sheath testing with DC voltage up to 10 kV
- Fault pre-location by means of high-resolution resistance measuring bridge
- Pre-location of cable sheath faults and faults due to earth contact with measuring bridge
- Step voltage method for cable sheath fault pin-pointing
Features
- Pre-location of cable sheath faults and faults due to earth contact
- Measuring bridge with automatic zero balancing
- Automatic evaluation
- High accuracy by accounting for different cable sections in terms of length, conductor cross-section and material
- Cable sheath fault pin-pointing
- Pulsed voltage up to 10 kV
- 4 pulse patterns selectable
- Adjustable switch-on delay and operating time
- General functions
- Continuously adjustable voltage
- Adjustable current and voltage limitation
- Automatic measurement sequences and reporting
- Automatic report export to USB stick
- Integrated discharge unit
- Connection for external emergency off unit in accordance with EN 50191
Baur Shirla Cable Sheath Testing and Fault Locator
- BAUR shirla sheath test and fault location device
- HV connection cable, 4.5 m, fix mounted
- 4-wire bridge connection cable, 2.5 m, fix mounted
- G-clamps, 24 mm, 4 pcs
- Short-circuit cable set
- Earth cable, 3 m, with earth terminal
- Transport case for accessories
- USB drive
- Carrying strap
- Mains supply cord, 2.5 m
- User manual